TM 10-7310-281-13&P
MODERN BURNER UNIT (MBU)
0009 00
TROUBLESHOOTING PROCEDURES
0009 00-6
THIS PROCEDURE COVERS:
Controller Error Codes
INITIAL SETUP:
Maintenance Level
Materials/Parts
Operator
None
EVALUATE
If any of the internal systems of the MBU experiences a malfunction, an error code may appear on the hour meter
display of the control panel. The following table lists the expected error codes and internal systems that may be
the cause of the malfunction. These error codes are not designed to specifically pinpoint the actual MBU
assembly at fault but may serve as an aid in narrowing down the source of the malfunction. If an error code
indicates a problem in an MBU subsystem that is not repairable at the Operator level, it must be referred to Unit
Maintenance.
Table 1. Controller Error Codes
Code
Meaning
Suggested Action
ER01
No Flame or flame-out
See troubleshooting procedure MBU fails to start or MBU shuts
down during operation
ER02
Overvoltage
Check voltage at power source. Check cables and connections
between power source and MBU.
ER03
Undervoltage
Check voltage at power source. Check cables and connections
between Power source and MBU.
ER04
Tank not full after4
minutes of fueling
See troubleshooting procedure MBU fails to refuel.
ER05
Flame detected
If there is a flame in the burner (when there should NOT be), then
extinguish it, or allow to burn out before attempting to operate burner
again. If no flame is present, then check flame sensor.
ER06
Fuel sensor
Check fuel sensor connection and wiring. Check fuel sensor.
ER07
Invalid key entry
Press STOP button to cancel error. Proceed with MBU operation. If
error persists, then check for sticking buttons.
ER09
Fuel solenoid valve or
Vent solenoid valve
Check fuel solenoid connection and wiring. Check vent solenoid
connection and wiring. Check fuel solenoid. Check vent solenoid.
ER0A
Air solenoid valve
Check air solenoid connection and wiring. Check air solenoid.
ER11
Compressor
Check compressor connection and wiring. Check compressor.
ER12
Ignitor
Check ignitor connection and wiring. Check ignitor.
ER13
Compressor or Ignitor
Check compressor connection and wiring. Check ignitor connection
and wiring. Check compressor. Check ignitor.
ER80
ER81
ER82
Controller
Cycle power. Attempt operation again. If error persists, replace
Controller.
END OF WORK PACKAGE