TM 10-5410-284-13&P
TM 10602A-13&P
LIGHTWEIGHT MAINTENANCE ENCLOSURE (LME)
0005 00
OPERATION UNDER USUAL CONDITIONS
0005 00-18
WARNING
Connecting External Power. Open power distribution box main cover latch located on the bottom of
the box (1) by depressing safety catch and pivoting cover (2) forward. Lift cover up all the way and
secure it with the hook and pile fastener strap/pad (3).Then proceed as follows:
Lethal voltage is present when the power distribution box is connected
to a power source. The generator should be off while the following
steps are performed. Serious injury or death by electrocution may
result if this warning is not followed.
Strip the outer jacket of the generator cable (4) approximately 4 inches long. Using a wire stripping tool,
strip individual wires (5) approximately ½ inch long.
Using a #2 flat head screwdriver, open terminal access cover (6), by turning 1/4 turn screw counter-
clockwise.
Route cable in through cord grip (7).
Position wires as follows under set screws (8) and secure with same screwdriver by tightening screws
clockwise:
BLACK WIRE
L1
RED WIRE
L2
BLUE WIRE
L3 (If provided)
WHITE WIRE
L0
GREEN WIRE
GROUND
Tighten cord grip (7) by hand until cable (4) is secure.
Close terminal access cover (6) and secure by turning 1/4 turn screw clockwise.
Plug male end of 25 foot light cord (9) into receptacle marked LIGHTS ONLY.
Power from generator may now be applied.
Test each receptacle by pressing the blue button (10) marked TEST.
Reset by pressing red button (11) marked RESET