TM 10-5411-200-14T.O. 35E4-177-14-6. (cont)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION5.ONE OR MORE FLUORESCENT LIGHTS IN THE FIXED SECTION FAIL TO COME ON.Step 1.Check visually for burned out fluorescent lamps.Replace lamp, (paragraph 4-12).Step 2.Test operation of fluorescent light fixture and wiring(paragraph 4-12).a.Replace defective wiring (paragraph 4-12).b.Replace defective light fixture (paragraph 4-12).WARNINGIn the event of lamp breakage, care must be taken inremoval of broken glass fragments and white phosphorousdust that may be dispersed within fixture.Inhalationof phosphorous dust could cause dangerous injury.6.NO POWER AT ONE OR MORE UTILITY OUTLETS IN THE EXPANDED SECTIONS.Step 1.Check and reset associated circuit breaker CB3, CB5, CB7.Replace defective circuit breaker (paragraph 4-7).Step 2.Test operation of utility outlet and wiring (paragraph4-13) .a.Replace defective wiring (paragraph 4-13).b.Replace defective outlet (paragraph 4-13).7.NO POWER AT ECU SUPPLY CONNECTOR.Step 1.Check and reset circuit breaker CB1.Replace defective circuit breaker (paragraph 4-7).Step 2.Test operation of connector and wiring (paragraph(4-8).a.Replace defective wiring (paragraph 4-8).b.Replace defective connector (paragraph 4-8).4-4