TM 10-5410-284-13&PTM 10602A-13&PLIGHTWEIGHT MAINTENANCE ENCLOSURE (LME)0008 00TROUBLESHOOTING PROCEDURES 0008 00-22.THIS PROCEDURE COVERS:Lights inoperativeINITIAL SETUP:Maintenance LevelMaterials/PartsOperatorBulb, 50 watt, double tube, 4 pinTable 0008 00--1. Troubleshooting Procedures - ContinuedMALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONLights inoperativeWARNINGLethal voltage is present whenlight set is connected to powersource. Disconnect powerbefore inspecting or repairingany part of the light set.1. If all lights are inoperative,1. Ensure an external powercheck external power and cablesource (commercial or aconnection to distribution boxgenerator providing 110V AC) isas in procedure 1.connected to distribution box.Refer to Work Package 0005-002. Check light circuit breaker at2. Reset light circuit breaker. distribution box.3. If only individual light(s) are3. Reconnect power cable(s)inoperative, check the powercorrectly.cable(s) for proper connection.4. Check fluorescent bulbs on4. Replace fluorescent bulbs onindividual, inoperative lights. individual, inoperative lights.Refer to Work Package 002000.5. If condition persists or lightcircuit breaker activatesrepeatedly, notify unitmaintenance.