TM 10-5410-284-13&P
TM 10602A-13&P
LIGHTWEIGHT MAINTENANCE ENCLOSURE (LME)
0008 00
TROUBLESHOOTING PROCEDURES
0008 00-1
1.
THIS PROCEDURE COVERS:
No power at distribution box
INITIAL SETUP:
Maintenance Level
Materials/Parts
Operator
None
Table 0008 00-1. Troubleshooting Procedures.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
No power at power distribution
box.
WARNING
Lethal voltage is present when
the power distribution box is
connected to a power source.
Disconnect the power source
before touching any wires in the
box.
1. Check external power supply
1. Ensure an external power
to distribution box and proper
source (commercial or genera-
connection to terminal block.
tor, providing 110V AC) is
properly connected to
distribution box terminal block.
Refer to Work Package 0005
00.
2. Check circuit breakers.
2. Reset circuit breakers.
3. If condition persists, notify
unit maintenance.